Emergency & Exit Lighting Testing
Emergency lighting is the cheapest deficiency in the building to fix and one of the most common to be written up for. The reason is simple: the units look fine. A battery that has quietly lost its capacity gives no outward sign at all — the light comes on when you press the button and dies four minutes into a real power failure.
That’s why Ontario requires more than a button press once a year. We run the full-duration test that actually proves the battery, replace what fails, and document the result.
What we actually do
Test battery units, remote heads and exit signs throughout the building — stairwells, corridors, lobbies, parking levels and mechanical rooms — under load for the full required duration, and confirm illumination levels along the exit path.
We replace failed batteries, lamps and heads, correct aiming, and flag areas where coverage has fallen short of what the building needs.
How often it’s due
Emergency lighting units should receive a monthly function test to confirm that each unit activates properly upon loss of power, typically performed by building staff. Annually, a full-duration test should be performed and documented by a qualified technician, with each unit operating under load for 30 minutes while maintaining the required level of illumination.
Why teams call us
A 30-minute test across a large building is slow, tedious work, and it is obvious in the results when a vendor has rushed it. We do it properly and report unit by unit, so you know which locations failed and where your next battery replacement budget is going.
Services we perform on this system
Inspection, Testing, & Maintenance
One coordinated inspection, testing and maintenance program for every life-safety system, scheduled to code and documented in one place.
Learn more →Repair & 24/7 Emergency Service
Corrective and emergency repair for sprinkler, alarm, pump, extinguisher, lighting, door and damper deficiencies, 24/7.
Learn more →Design, Installation & Retrofit
Engineered design, permit drawings and full installation of fire alarm, sprinkler and standpipe systems — including retrofits and upgrades in…
Learn more →Frequently asked questions
How long does emergency lighting have to stay on in Ontario?
The units must maintain the required illumination for 30 minutes under load, and that’s what the annual test proves. A monthly button press only confirms the unit switches on — it says nothing about how long the battery will last.
Can our staff do the monthly test?
Yes, and it’s the owner’s responsibility to see it happens. The annual full-duration test is the one that needs a qualified technician and a proper record.
Half our units failed. Is that normal?
For a building that hasn’t had a real duration test in a few years, unfortunately yes. Sealed batteries degrade on a predictable curve, and the failures tend to arrive together. We’ll give you a unit-by-unit list so you can plan the replacement rather than absorb it all at once.
Is your building in full compliance?
Get in touch and learn how we can bring your building to full fire & life-safety compliance.