Fire Pump Testing & Service
A fire pump either makes its rated pressure and flow or it doesn’t, and there is exactly one way to find out. Everything above the lower floors of your building depends on the answer — if the pump underperforms, the sprinklers and standpipes it feeds underperform with it.
We run the weekly and monthly no-flow tests, carry out the annual full-flow performance test, and service the pump, driver and controller as one system rather than three separate items on a report.
What we actually do
No-flow (churn) testing, and annual full-flow performance testing at rated capacity and at 150% of rated capacity, plotted against the pump’s original curve so you can see performance trending over the years — not just a pass or fail.
We service controllers and transfer switches, jockey pumps, packing and bearings, and for diesel units the batteries, fuel quality, cooling and exhaust.
How often it is due
Fire pump testing and maintenance should be performed on a regular schedule. Diesel fire pumps require a weekly no-flow test, while electric fire pumps require a monthly no-flow test. Annually, a full-flow performance test should be completed, along with controller servicing and driver maintenance.
Why teams call us
Full-flow testing is as much a logistics problem as a technical one. It needs hoses or a flow meter, a plan for where several thousand litres a minute will go, and coordination with the building so the water ends up somewhere harmless. Downtown, in a tight loading area, that planning is the job. We do it without flooding your garage.
Services we perform on this system
Inspection, Testing, & Maintenance
One coordinated inspection, testing and maintenance program for every life-safety system, scheduled to code and documented in one place.
Learn more →Repair & 24/7 Emergency Service
Corrective and emergency repair for sprinkler, alarm, pump, extinguisher, lighting, door and damper deficiencies, 24/7.
Learn more →Design, Installation & Retrofit
Engineered design, permit drawings and full installation of fire alarm, sprinkler and standpipe systems — including retrofits and upgrades in…
Learn more →Fire Alarm Monitoring
24/7 central-station monitoring of fire alarm and sprinkler signals, with immediate dispatch and a full event log.
Learn more →Frequently asked questions
What’s the difference between the weekly test and the annual test?
The weekly or monthly test runs the pump without flowing water — it confirms the pump starts and runs. The annual test flows water at full rated capacity and beyond, which is the only test that proves the pump can still deliver what the building was designed around.
Where does all the water go during a full-flow test?
That’s the first thing we plan. Depending on the building we use hose to a safe discharge point or a closed-loop flow meter that returns water to the suction side. We’ll walk the site and confirm the approach before test day.
Our pump passed but the numbers were lower than last year. Should we worry?
Worth paying attention to. A pump that’s trending down over several annual tests is telling you something before it fails. That’s why we plot results against the original curve and keep your history — a single pass tells you less than five years of results.
Is your building in full compliance?
Get in touch and learn how we can bring your building to full fire & life-safety compliance.